Automation And Power Solutions Est. (A&P Solutions), is a Multinational Company with diversified and multi-disciplinary Contracting, Trading and Training activities ranging.
HQ-M1200 KVA Modular UPS – a scalable UPS device offering flexibility with 50kVA UPS modules (available in the range of 800kVA to 1200kVA). This UPS power supply is engineered for reliability and efficiency, providing adaptable power solutions for a wide range of industry applications.
ABOUT HQ-MR ONLINE RACKMOUNT MODULAR UPS
Applications: This double conversion ups power supply is suitable for data centers, finance, banking critical infrastructure, commercial buildings, industrial complexes, healthcare, telecommunications bases, process control equipment and more.
SPECIFICATION
| Model | HQ-M200 | HQ-M300 | HQ-M400 | HQ-M500 | HQ-M600 | HQ-M800 | HQ-M1200 |
| Capacity | 200kVA | 300kVA | 400kVA | 540kVA | 600kVA | 800kVA | 1200KVA |
| Cabinet Type | 5(4+1) Modules | 7(6+1/5+2) Modules | 12(8+4) Modules | 12(10+2) Modules | 12 Modules | 14 Modules | 24 Modules |
| Power Module Capacity | 50/60kVA | 60kVA | 50/60Kva | ||||
| Input | |||||||
| Rated Voltage | 3 Phase+N+PE 380/400/415VAC (Line voltage) | ||||||
| Rated Frequency | 50/60Hz | ||||||
| Voltage Range | 304~478 VAC (line-line) full load; 304 VAC ~228 VAC (line-line) load derating linearly from 100% to 80% | ||||||
| Frequency Range | 40 ~ 70Hz | ||||||
| Power Factor | ≥0.99 | ||||||
| THDi | <3% (linear load); <5% (nonlinear load) | ||||||
| Output | |||||||
| Rated Voltage | 380/400/415VAC (Line Voltage) | ||||||
| Voltage Accuracy | ≤±1.0% @ balanced load;≤±5.0% @ unbalanced load | ||||||
| Frequency Tracking Range | ±0.5Hz ~ ±5Hz, configurable, default: ±3Hz | ||||||
| Overload | ≤105%,long run; 105% ~ 110%,60min; 110 ~ 125%,10min;125~150%,1min; >150%,200ms | ||||||
| Power Factor | 1 | ||||||
| THDu | ≤2% @ (100% linear load);≤4% @ (100% nonlinear load) | ||||||
| Crest Factor | 3:1 | ||||||